1、额定电压U0/U为300/500V;电缆导体的长期工作温度:聚氯乙烯绝缘为70℃、105℃两种,聚乙烯绝缘为70℃,交联聚乙烯绝缘为90℃(绝缘交联类型可分为硅烷交联和辐照交联)。敷设电缆时的环境温度不低于0℃。电缆允许在环境温度-40~50℃,相对湿度不大于80%时作固定敷设或移动使用。
1. The rated voltage U0/U is 300/500V; the long-term operating temperature of the cable conductor is 70 ℃ and 105 ℃ for polyvinyl chloride insulation, 70 ℃ for polyethylene insulation, and 90 ℃ for cross-linked polyethylene insulation (insulation cross-linking types can be divided into silane cross-linking and irradiation cross-linking). The ambient temperature during cable laying shall not be lower than 0 ℃. Cables are allowed to be fixedly laid or moved for use in environments with temperatures ranging from -40 to 50 ℃ and relative humidity not exceeding 80%.
2、敷设安装电缆时的***小弯曲半径:无铠装层的电缆,应不小于电缆外径的6倍,有铠装结构的电缆,应不小于电缆外径的12倍,有屏蔽层结构的软电缆,应不小于电缆外径的10倍。
2. The minimum bending radius for laying and installing cables: for cables without armor layer, it should not be less than 6 times the outer diameter of the cable; for cables with armor structure, it should not be less than 12 times the outer diameter of the cable; for flexible cables with shielding layer structure, it should not be less than 10 times the outer diameter of the cable.